Transformer Based 1/1 Phase UPS
Cabinet power range 15 kVA, 20 kVA and 30 kVA.
MP1100 series UPS adopt the globally most advanced DSP digital control technique, with voice call send-alerting alarming function, a high-speed microprocessor (MCU), a programmable logic device (CPLD), the sixth generation IGBT and static state switch. Combined it has a dissipation with exhausts HP high power, which enters into deducing digital ages of classic legend, bring up with the big capacity, high reliability, the stability of function to reside global top-grade level.
MP1100 series UPS’s 15kVA, 20kVA and 30kVA, by means of 100% network environments adaptability, which are widely used in the network office environment of following sides such as BCS billing center of communications, BCS BTS communication stations, the banking business outlets, ATM cash dispensers, stock exchange firms, transportation, electric power, industry and any other profession vocation.
Model | MP1115K | MP1120K | MP1130K |
---|---|---|---|
Capacity | 15kVA | 20kVA | 30kVA |
Power Watt | 12kW | 16kW | 24kW |
Working Principal | Low-Frequency Transformer Based True On Line-Double Conversion | Low-Frequency Transformer Based True On Line-Double Conversion | Low-Frequency Transformer Based True On Line-Double Conversion |
RECTIFIER (INPUT) | |||
Phase | Single Phase | Single Phase | Single Phase |
Input Power Factor | ≧0.9 (Plus Filter) | ≧0.9 (Plus Filter) | ≧0.9 (Plus Filter) |
Input Voltage Range | 220VAC (230VAC or 240VAC) ±25%, 1P+N+PE optional 110V (120V or 277V) | 220VAC (230VAC or 240VAC) ±25%, 1P+N+PE optional 110V (120V or 277V) | 220VAC (230VAC or 240VAC) ±25%, 1P+N+PE optional 110V (120V or 277V) |
Input Frequency Range | 50Hz ±10% 60Hz ±10% (Selectable) | 50Hz ±10% 60Hz ±10% (Selectable) | 50Hz ±10% 60Hz ±10% (Selectable) |
Output Ripple | Less than 2% | Less than 2% | Less than 2% |
Soft Start | 0 up to 100% 5sec | 0 up to 100% 5sec | 0 up to 100% 5sec |
CHARGING | |||
Charging Mode | Constant current, then constant voltage, and charge with temperature compensation | Constant current, then constant voltage, and charge with temperature compensation | Constant current, then constant voltage, and charge with temperature compensation |
Float Charging Voltage | 220VDC | 220VDC | 220VDC |
Equalized Charging Voltage | 227VDC | 227VDC | 227VDC |
Temp. Compensated Voltage | -3mV / ℃ / Cell | -3mV / ℃ / Cell | -3mV / ℃ / Cell |
Charging Current | 5 – 10A | 5 – 10A | 5 – 10A |
BATTERY | |||
Type | VRLA / AGM / Gel, optional Lithium Battery | VRLA / AGM / Gel, optional Lithium Battery | VRLA / AGM / Gel, optional Lithium Battery |
Battery Capacity | 7 up to 999AH settable (Configure Battery Capacity according to Back-up Time) | 7 up to 999AH settable (Configure Battery Capacity according to Back-up Time) | 7 up to 999AH settable (Configure Battery Capacity according to Back-up Time) |
Quantity | 16 units 12V or 96 units 2V batteries (Battery Voltage 192VDC) | 16 units 12V or 96 units 2V batteries (Battery Voltage 192VDC) | 16 units 12V or 96 units 2V batteries (Battery Voltage 192VDC) |
Temperature | 20ºC up to 25ºC (For Maximum Efficiency) | 20ºC up to 25ºC (For Maximum Efficiency) | 20ºC up to 25ºC (For Maximum Efficiency) |
INVERTER (OUTPUT) | |||
Phase | Single Phase | Single Phase | Single Phase |
Nominal Voltage | 220VAC (230VAC or 240VAC), 1P + N optional 110V (120V or 277V) | 220VAC (230VAC or 240VAC), 1P + N optional 110V (120V or 277V) | 220VAC (230VAC or 240VAC), 1P + N optional 110V (120V or 277V) |
Output Voltage Regulated Accuracy | ±1% (Stable load) ±3% (Fluctuant load) | ±1% (Stable load) ±3% (Fluctuant load) | ±1% (Stable load) ±3% (Fluctuant load) |
Output Frequency Range | 50Hz – 60Hz less than ±0.5% (Asynchronous) | 50Hz – 60Hz less than ±0.5% (Asynchronous) | 50Hz – 60Hz less than ±0.5% (Asynchronous) |
Crest Factor | Greater than 3:1 | Greater than 3:1 | Greater than 3:1 |
Output Total Harmonic
Distortion (THD) | Pure Sine Wave Linear Load less than 3% Non-Linear Load less than 5% | Pure Sine Wave Linear Load less than 3% Non-Linear Load less than 5% | Pure Sine Wave Linear Load less than 3% Non-Linear Load less than 5% |
Dynamic Characteristics | Instant voltage less than ±5% (0 – 100%) Instant recover time less than 10ms | Instant voltage less than ±5% (0 – 100%) Instant recover time less than 10ms | Instant voltage less than ±5% (0 – 100%) Instant recover time less than 10ms |
Overload Capacity | At 115% load, normal work At 125% load 10 min At 150% load 1min At 200% load 1sec | At 115% load, normal work At 125% load 10 min At 150% load 1min At 200% load 1sec | At 115% load, normal work At 125% load 10 min At 150% load 1min At 200% load 1sec |
Inverter Efficiency | Greater than 92% (full load) | Greater than 92% (full load) | Greater than 92% (full load) |
BYPASS | |||
Phase | Single Phase (P+N) | Single Phase (P+N) | Single Phase (P+N) |
Nominal Voltage | 220VAC (230VAC or 240VAC) optional 110V (120V or 277V) | 220VAC (230VAC or 240VAC) optional 110V (120V or 277V) | 220VAC (230VAC or 240VAC) optional 110V (120V or 277V) |
Transfer Time | 0ms (adopt static switch) | 0ms (adopt static switch) | 0ms (adopt static switch) |
PROTECTION FUNCTION | |||
Input Protection | Input voltage, frequency over limited protection | Input voltage, frequency over limited protection | Input voltage, frequency over limited protection |
Output Protection | Over current, short circuit, over voltage, low voltage | Over current, short circuit, over voltage, low voltage | Over current, short circuit, over voltage, low voltage |
Battery Protection | Over charge, over-discharge protection | Over charge, over-discharge protection | Over charge, over-discharge protection |
Temperature Protection | Environment over temperature protection, inverter over temperature protection | Environment over temperature protection, inverter over temperature protection | Environment over temperature protection, inverter over temperature protection |
Hardware Fault Protection | Assistant power abnormal, breaker cut off, breaker overload, power devices over current/over voltage etc. protection | Assistant power abnormal, breaker cut off, breaker overload, power devices over current/over voltage etc. protection | Assistant power abnormal, breaker cut off, breaker overload, power devices over current/over voltage etc. protection |
GENERAL SYSTEM PARAMETERS | |||
Working Environment | Temp: -10 up to 40ºC, Relative humidity: 30% up to 90% Altitude less than 2000m (1% decrease against 100m rise, Max. altitude 4000m) | Temp: -10 up to 40ºC, Relative humidity: 30% up to 90% Altitude less than 2000m (1% decrease against 100m rise, Max. altitude 4000m) | Temp: -10 up to 40ºC, Relative humidity: 30% up to 90% Altitude less than 2000m (1% decrease against 100m rise, Max. altitude 4000m) |
Cooling Method | COMPULSIVE VENTILATION | COMPULSIVE VENTILATION | COMPULSIVE VENTILATION |
Communication Interface | RS232 / RS485, optional dry contact, SNMP card (for remote control via internet) | RS232 / RS485, optional dry contact, SNMP card (for remote control via internet) | RS232 / RS485, optional dry contact, SNMP card (for remote control via internet) |
Parallel Operation | Tandem hot backup | Tandem hot backup | Tandem hot backup |
Auto-surge Capacity | 10 / 700μS 5KV; 8 / 20μS 20KA | 10 / 700μS 5KV; 8 / 20μS 20KA | 10 / 700μS 5KV; 8 / 20μS 20KA |
Protection Level | IP21 | IP21 | IP21 |
Safety Performance | Vin-n Vout-n 2000Vac, creepage less than 10mA, insulating resistance greater than 2MΩ (500VDC) | Vin-n Vout-n 2000Vac, creepage less than 10mA, insulating resistance greater than 2MΩ (500VDC) | Vin-n Vout-n 2000Vac, creepage less than 10mA, insulating resistance greater than 2MΩ (500VDC) |
Noise (dB) | 55 up to 60 | 55 up to 60 | 55 up to 60 |
Dimension (W*D*H) mm | 450 * 600 * 1200 | 450 * 600 * 1200 | 450 * 600 * 1200 |
Weight (Kg) | 186 | 201 | 251 |