BKH M2 UPS

Cabinet power range 20 kVA – 200 kVA.

BKH series UPS single cabinet power range 20kVA up to 600kVA can be customized depending on loads and can support 4 units in parallel.

Production capability has a max capacity of 2.4MVA.  The world-class digital UPS, with the latest 9 leading technology, all data index have reached modular UPS standard YD/T2165-2010 class 1 standard.

A reliable and highly competitive power supply for all industry.

BKH – M2AT60KT100KT160KT200K
Capacity20kVA – 60kVA20kVA – 100kVA20kVA – 160kVA20kVA – 200kVA
Power Module Capacity20kVA20kVA20kVA20kVA
Module Size
W * D * H
pendingpendingpendingpending
Module Weight28Kg / Unit28Kg / Unit28Kg / Unit28Kg / Unit
Physical Parameter
Cabinet Size mm
W * D * H
600 * 800 * 1250600 * 1100 * 2000600 * 1100 * 2000600 * 1100 * 2000
Cabinet Weight130Kg295Kg305Kg310Kg
Modules Number (Max)35810
Mains Input (AC)
Phase3 phase + N + PE3 phase + N + PE3 phase + N + PE3 phase + N + PE
Voltage Range291V up to 492V (line-line) full load
200V up to 291V linearly decrease
291V up to 492V (line-line) full load
200V up to 291V linearly decrease
291V up to 492V (line-line) full load
200V up to 291V linearly decrease
291V up to 492V (line-line) full load
200V up to 291V linearly decrease
Frequency Range35Hz up to 70Hz35Hz up to 70Hz35Hz up to 70Hz35Hz up to 70Hz
THDiLess than 3% (Full linear load)Less than 3% (Full linear load)Less than 3% (Full linear load)Less than 3% (Full linear load)
Power Factor0.9950.9950.9950.995
Bypass Range-10% up to 10%
(Customized: -10% up to -30% and 10% up to 20%)
-10% up to 10%
(Customized: -10% up to -30% and 10% up to 20%)
-10% up to 10%
(Customized: -10% up to -30% and 10% up to 20%)
-10% up to 10%
(Customized: -10% up to -30% and 10% up to 20%)
Battery
Connection TypePositive series and negative series batteryPositive series and negative series batteryPositive series and negative series batteryPositive series and negative series battery
Rated Voltage+/- 240VDC (Positive and negative series, each 20pcs * 12V)
Can be customized
+/- 240VDC (Positive and negative series, each 20pcs * 12V)
Can be customized
+/- 240VDC (Positive and negative series, each 20pcs * 12V)
Can be customized
+/- 240VDC (Positive and negative series, each 20pcs * 12V)
Can be customized
Battery Number40pcs / set (Can be customized from 30pcs up to 50pcs / set)40pcs / set (Can be customized from 30pcs up to 50pcs / set)40pcs / set (Can be customized from 30pcs up to 50pcs / set)40pcs / set (Can be customized from 30pcs up to 50pcs / set)
Charging Current20% * System power (battery capacity)20% * System power (battery capacity)20% * System power (battery capacity)20% * System power (battery capacity)
Output (Inverter)
Output Voltage380VAC 3 phase 4 wires + PE380VAC 3 phase 4 wires + PE380VAC 3 phase 4 wires + PE380VAC 3 phase 4 wires + PE
Voltage RegulationLess than +/- 1%
Phase Lock Range50Hz / 60Hz +/-5Hz;
(Self frequency 50Hz / 60Hz +/-0.01Hz)
50Hz / 60Hz +/-5Hz;
(Self frequency 50Hz / 60Hz +/-0.01Hz)
50Hz / 60Hz +/-5Hz;
(Self frequency 50Hz / 60Hz +/-0.01Hz)
50Hz / 60Hz +/-5Hz;
(Self frequency 50Hz / 60Hz +/-0.01Hz)
Output Frequency50Hz / 60Hz +/-0.01
(Turn into mains frequency if phase locked)
50Hz / 60Hz +/-0.01
(Turn into mains frequency if phase locked)
50Hz / 60Hz +/-0.01
(Turn into mains frequency if phase locked)
50Hz / 60Hz +/-0.01
(Turn into mains frequency if phase locked)
Power Factor1111
Crest Factor3:13:13:13:1
THDuTHD less than 2% (linear load)
THD less than 3% (non-linear load)
THD less than 2% (linear load)
THD less than 3% (non-linear load)
THD less than 2% (linear load)
THD less than 3% (non-linear load)
THD less than 2% (linear load)
THD less than 3% (non-linear load)
Three Phase Voltage Unbalance DegreeBalance load: 0.5% 100% unbalance load : 1%Balance load: 0.5% 100% unbalance load : 1%Balance load: 0.5% 100% unbalance load : 1%Balance load: 0.5% 100% unbalance load : 1%
Dynamic Voltage Transient RangeLess than 3%Less than 3%Less than 3%Less than 3%
Transient Recovery Time0ms0ms0ms0ms
Three Phase Voltage DeviationMains: 0.4
Battery: 0.3
Mains: 0.4
Battery: 0.3
Mains: 0.4
Battery: 0.3
Mains: 0.4
Battery: 0.3
Overload Capacity125% for 10min
150% for 1min
Greater than 150% for 200ms (linear load)
125% for 10min
150% for 1min
Greater than 150% for 200ms (linear load)
125% for 10min
150% for 1min
Greater than 150% for 200ms (linear load)
125% for 10min
150% for 1min
Greater than 150% for 200ms (linear load)
System EfficiencyGreater than 96%Greater than 96%Greater than 96%Greater than 96%
Environment Indicator
NoiseLess than 60dB @100% load,
cooling fan adopt intelligent speed control
Less than 60dB @100% load,
cooling fan adopt intelligent speed control
Less than 60dB @100% load,
cooling fan adopt intelligent speed control
Less than 60dB @100% load,
cooling fan adopt intelligent speed control
DisplayTouch screen LCD+LEDTouch screen LCD+LEDTouch screen LCD+LEDTouch screen LCD+LED
InterfaceStandard: RS232, RS485,
Dry contacts,
SNMP card optional
Standard: RS232, RS485,
Dry contacts,
SNMP card optional
Standard: RS232, RS485,
Dry contacts,
SNMP card optional
Standard: RS232, RS485,
Dry contacts,
SNMP card optional
Operation TemperatureTemperature: -10ºC up to 40ºC
Humidity 0% up to 98%
Storage temperature -25ºC up to 75ºC
Altitude (m): less than 1000m, 1000m-2000m above every 100m reduce 1%
Temperature: -10ºC up to 40ºC
Humidity 0% up to 98%
Storage temperature -25ºC up to 75ºC
Altitude (m): less than 1000m, 1000m-2000m above every 100m reduce 1%
Temperature: -10ºC up to 40ºC
Humidity 0% up to 98%
Storage temperature -25ºC up to 75ºC
Altitude (m): less than 1000m, 1000m-2000m above every 100m reduce 1%
Temperature: -10ºC up to 40ºC
Humidity 0% up to 98%
Storage temperature -25ºC up to 75ºC
Altitude (m): less than 1000m, 1000m-2000m above every 100m reduce 1%
IP ClassIP30 (Removable dust filter)IP30 (Removable dust filter)IP30 (Removable dust filter)IP30 (Removable dust filter)

NOTE: Subject to changes without further notice!