BKH M1 UPS

Cabinet power range 10 kVA – 120 kVA.

BKH – M1 UPS power range 10kVA-120kVA can be configured to 1P/1P, 3P/1P, 3P/3P, 1P/3P without derating.

It has a first-class technical index due to the latest IGBT technology incorporated in our concepts of green energy, environment protection, energy saving and state-of-the-art design. It has been based on our independent R&D of hot-swappable technology. The BKH – M1 UPS provide our customers with more flexibility, reliable, functional and affordable UPS systems with a top-notch quality.

BKH – M1A
(Full configured)
G30KG60KG100KG120K
Capacity10kVA – 30kVA10kVA – 60kVA10kVA – 100kVA10kVA – 120kVA
Power Module Capacity10kVA10kVA10kVA10kVA
Power Module Weight14Kg14Kg14Kg14Kg
Power Module Number
(MAX)
361012
Physical Parameter
Power Module Size mm
W * D * H
pendingpendingpendingpending
Power Module Weight14Kg / Unit14Kg / Unit14Kg / Unit14Kg / Unit
Cabinet Size mm
W * D * H
600 * 800 * 1600600 * 800 * 1600600 * 800 * 2000600 * 800 * 2000
Cabinet Weight180Kg197Kg245Kg260Kg
Mains Input (AC)
Phase3 phase 4 wires / 1 phase 2 wires + G3 phase 4 wires / 1 phase 2 wires + G3 phase 4 wires / 1 phase 2 wires + G3 phase 4 wires / 1 phase 2 wires + G
Voltage Range291V up to 492V (line-line) full load291V up to 492V (line-line) full load291V up to 492V (line-line) full load291V up to 492V (line-line) full load
Frequency Range30Hz up to 80Hz30Hz up to 80Hz30Hz up to 80Hz30Hz up to 80Hz
THDiLess than 3%Less than 3%Less than 3%Less than 3%
Power Factor0.9950.9950.9950.995
Bypass Range-10% up to 10%
(Customized: -10% up to -30% and 10% up to 20%)
-10% up to 10%
(Customized: -10% up to -30% and 10% up to 20%)
-10% up to 10%
(Customized: -10% up to -30% and 10% up to 20%)
-10% up to 10%
(Customized: -10% up to -30% and 10% up to 20%)
Battery
Connection TypePositive and negative battery supplyPositive and negative battery supplyPositive and negative battery supplyPositive and negative battery supply
Rated Voltage+/- 384VDC (+/- 32 * 12V series)+/- 384VDC (+/- 32 * 12V series)+/- 384VDC (+/- 32 * 12V series)+/- 384VDC (+/- 32 * 12V series)
Battery Number64 pcs / set64 pcs / set64 pcs / set64 pcs / set
Charging Current20% * System power (battery capacity)20% * System power (battery capacity)20% * System power (battery capacity)20% * System power (battery capacity)
Output (Inverter)
Output Voltage3 phase 380VAC / 1 phase 220VAC + G3 phase 380VAC / 1 phase 220VAC + G3 phase 380VAC / 1 phase 220VAC + G3 phase 380VAC / 1 phase 220VAC + G
Voltage RegulationLess than +/- 1%Less than +/- 1%Less than +/- 1%Less than +/- 1%
Phase Lock Range50Hz / 60Hz +/-5Hz;
(Self frequency 50Hz / 60Hz +/-0.01Hz)
50Hz / 60Hz +/-5Hz;
(Self frequency 50Hz / 60Hz +/-0.01Hz)
50Hz / 60Hz +/-5Hz;
(Self frequency 50Hz / 60Hz +/-0.01Hz)
50Hz / 60Hz +/-5Hz;
(Self frequency 50Hz / 60Hz +/-0.01Hz)
Output Frequency50Hz / 60Hz +/-0.01Hz
(If phase locked then mains frequency)
50Hz / 60Hz +/-0.01Hz
(If phase locked then mains frequency)
50Hz / 60Hz +/-0.01Hz
(If phase locked then mains frequency)
50Hz / 60Hz +/-0.01Hz
(If phase locked then mains frequency)
Power Factor0.90.90.90.9
Crest Factor3:13:13:13:1
THDuTHD less than 1% (linear load)
THD less than 3% (non-linear load)
THD less than 1% (linear load)
THD less than 3% (non-linear load)
THD less than 1% (linear load)
THD less than 3% (non-linear load)
THD less than 1% (linear load)
THD less than 3% (non-linear load)
Three Phase Voltage Unbalance DegreeBalance load: 0.2% 100% unbalance load : 0.5%Balance load: 0.2% 100% unbalance load : 0.5%Balance load: 0.2% 100% unbalance load : 0.5%Balance load: 0.2% 100% unbalance load : 0.5%
Dynamic Voltage Transient RangeLess than 2%Less than 2%Less than 2%Less than 2%
Transient Recovery Time0ms0ms0ms0ms
Three Phase Voltage DeviationMains: 0.1
Battery: 0.1
Mains: 0.1
Battery: 0.1
Mains: 0.1
Battery: 0.1
Mains: 0.1
Battery: 0.1
Overload Capacity125% for 10min
150% for 1min
Greater than 150% for 200ms (linear load)
125% for 10min
150% for 1min
Greater than 150% for 200ms (linear load)
125% for 10min
150% for 1min
Greater than 150% for 200ms (linear load)
125% for 10min
150% for 1min
Greater than 150% for 200ms (linear load)
System EfficiencyGreater than 94%Greater than 94%Greater than 94%Greater than 94%
Environment Indicator
NoiseLess than 60dB @100% load,
cooling fan adopt intelligent speed control
Less than 60dB @100% load,
cooling fan adopt intelligent speed control
Less than 60dB @100% load,
cooling fan adopt intelligent speed control
Less than 60dB @100% load,
cooling fan adopt intelligent speed control
DisplayTouch screen LCD+LEDTouch screen LCD+LEDTouch screen LCD+LEDTouch screen LCD+LED
InterfaceStandard: RS232, RS485,
Dry contacts,
SNMP card optional
Standard: RS232, RS485,
Dry contacts,
SNMP card optional
Standard: RS232, RS485,
Dry contacts,
SNMP card optional
Standard: RS232, RS485,
Dry contacts,
SNMP card optional
Operation TemperatureTemperature: -10ºC up to 40ºC
Humidity 0% up to 98%
Storage temperature -25ºC up to 75ºC
Altitude (m): less than 1000m, 1000m-2000m above every 100m reduce 1%
Temperature: -10ºC up to 40ºC
Humidity 0% up to 98%
Storage temperature -25ºC up to 75ºC
Altitude (m): less than 1000m, 1000m-2000m above every 100m reduce 1%
Temperature: -10ºC up to 40ºC
Humidity 0% up to 98%
Storage temperature -25ºC up to 75ºC
Altitude (m): less than 1000m, 1000m-2000m above every 100m reduce 1%
Temperature: -10ºC up to 40ºC
Humidity 0% up to 98%
Storage temperature -25ºC up to 75ºC
Altitude (m): less than 1000m, 1000m-2000m above every 100m reduce 1%
IP ClassIP30 (Removable dust filter)IP30 (Removable dust filter)IP30 (Removable dust filter)IP30 (Removable dust filter)

NOTE: Subject to changes without further notice!